How often should PAT testing be done?
There is no fixed legal interval. HSE says it depends on the type of equipment and where it is used. In an office, HSE suggests testing earthed kit such as kettles every 1 to 2 years.
Key facts
- HSE’s office table suggests no PAT test at all for double-insulated screens, fans and lamps, only a visual inspection every 2 to 4 years.
- In an office, HSE suggests a PAT test every 1 to 2 years for earthed kit such as kettles, and none for double-insulated computers.
- On a building site, HSE suggests testing 110V tools every 3 months and 230V tools every month.
- Hire equipment should be inspected and tested before each hire.
- You set the retest date as duty holder, not the person doing the test.
HSE’s suggested starting intervals for low-risk workplaces
This table is HSE’s own, from its leaflet INDG236 for offices, shops, hotels, care homes and other low-risk environments. The intervals are a starting point, not a rule.
| Equipment | User checks | Formal visual inspection | Combined inspection and testing |
|---|---|---|---|
| Battery-operated (under 40 volts) | No | No | No |
| Extra low voltage (under 50 volts AC), such as phones and low-voltage desk lights | No | No | No |
| Desktop computers and screens | No | Yes, 2 to 4 years | No if double insulated, otherwise up to 5 years |
| Photocopiers and fax machines, not hand-held and rarely moved | No | Yes, 2 to 4 years | No if double insulated, otherwise up to 5 years |
| Double insulated (Class II), not hand-held, moved occasionally, such as fans and table lamps | No | Yes, 2 to 4 years | No |
| Double insulated (Class II), hand-held, such as some floor cleaners and kitchen equipment | Yes | Yes, 6 months to 1 year | No |
| Earthed (Class I), such as kettles, irons, some floor cleaners and kitchen equipment | Yes | Yes, 6 months to 1 year | Yes, 1 to 2 years |
| Cables, leads, plugs, mains extension leads and battery chargers | Yes | Yes, 6 months to 4 years depending on what they connect to | Yes, 1 to 5 years depending on what they connect to |
HSE adds three notes. Leads and plugs fixed to Class II equipment are looked after as part of that equipment, while loose leads are treated as separate items. When you group equipment for testing, use the shortest interval in the group. And over time your results will show whether you can check less often, or need to check more.
Intervals for building sites, workshops and hire
Most guides stop at the office table. HSE’s fuller guidance, HSG107 Maintaining portable electrical equipment, has the same table extended to higher-risk work. These are the rows it adds.
| Type of work | User checks | Formal visual inspection | Combined inspection and testing |
|---|---|---|---|
| Equipment hire | Not applicable | Before issue and after return | Before issue |
| Construction, 110V equipment | Weekly | Monthly | Before first use on site, then every 3 months |
| Construction, 230V equipment | Daily or every shift | Weekly | Before first use on site, then monthly |
| Construction, fixed RCDs | Daily or every shift | Weekly | Before first use on site, then every 3 months (portable RCDs monthly) |
| Construction, equipment in site offices | Monthly | Every 6 months | Before first use on site, then yearly |
| Heavy industrial, or high risk of damage (not construction) | Daily | Weekly | Every 6 to 12 months |
| Light industrial | Yes | Before first use, then every 6 months | Every 6 to 12 months |
HSG107 says plainly that these suggested intervals are not legal requirements. Where it gives a range, the shorter interval is for more demanding conditions of use and the longer one is for less demanding conditions. It also says the IET Code of Practice has a similar table, set out differently, and that the two are considered consistent.
How to pick a number from a range
A range such as 1 to 2 years is an invitation to think about how hard each item works. A kettle boiled thirty times a day in a busy staff kitchen sits at the short end, so test it every year. The same model in a meeting room used twice a week can sit at the long end. Put the interval you chose, and the reason, in your register. If anyone asks why, the answer is written down.
Why the right answer depends on where it is used
HSE’s own example is a power tool on a construction site, which should be examined more often than a lamp in a hotel bedroom. HSG107 lists what to weigh up for each item.
- Whether it is earthed or double insulated
- Whether it is hand-held, since a fault in something you are holding is the one most likely to give you a shock
- The manufacturer’s recommendations, and the age and condition of the item
- Where it is used, and whether it could get wet, dusty or damaged
- How often it is used, and how it might be misused
- Any modifications or repairs, and what your past records show
Equipment used by the public needs more attention too. HSG107 says that where people use equipment you do not control, such as hairdryers in hotel rooms, formal visual inspections may need to be much more frequent.
The three kinds of check
- User checks are a quick look by the person using the item, every time, for damage to the plug, cable or case.
- Formal visual inspections are a closer look by someone trained, at set intervals, including inside the plug where it can be opened.
- Combined inspection and testing adds a PAT test, which finds faults you cannot see, such as a broken earth wire inside a cable or insulation that has broken down.
HSG107 says the full test can be done less often when your scheme includes formal visual inspections and keeps an eye on user checks. That is why the tables give longer intervals to testing than to looking.
How an office of 25 people plans its first year
The office manager lists 74 items and gives each one an interval from HSE’s low-risk table. This is the plan for the first year.
| Item | How many | Type | Visual inspection every | PAT test every | PAT tests due this year |
|---|---|---|---|---|---|
| Kettles and the microwave | 4 | Class I, earthed | 6 months to 1 year | 1 to 2 years | 4 |
| Desk fans and lamps | 12 | Class II, not hand-held | 2 to 4 years | No test | 0 |
| Hand-held vacuum and hairdryer | 2 | Class II, hand-held | 6 months to 1 year | No test | 0 |
| Desktop computers | 15 | Class I, rarely moved | 2 to 4 years | Up to 5 years, last done 2 years ago | 0 |
| Screens | 15 | Class II | 2 to 4 years | No test | 0 |
| Photocopier | 1 | Class I, rarely moved | 2 to 4 years | Up to 5 years, now due | 1 |
| Extension leads | 10 | Lead | 6 months to 4 years | 1 to 5 years | 10 |
| Laptop chargers | 15 | Battery charger, Class II | 6 months to 4 years | Visual only | 0 |
| Total | 74 | 15 |
Of 74 items, 15 need a PAT test this year and the rest need a visual inspection. That is a short session with a handheld tester, and the visual inspections can be spread across the year. In year two the kettles and microwave are due again, because they sit at the short end of their range in a busy kitchen.
What HSE did in its own example cases
HSE publishes two short case studies that show the thinking in practice.
A high street travel agent found computers, a fax, two printers and a vacuum cleaner. The computers and printers were rarely moved and their cables were out of the way, so the manager chose a visual inspection every 5 years. The vacuum was heavily used and had already needed its cable repaired, so it got a visual inspection every 6 months and a test after 12 months, with a review after 24 months.
HSE also reviewed its own offices in 2011. Looking back over five years of annual test results, it decided further PAT tests were not needed for the foreseeable future, or at all, for certain types of equipment. It kept user checks and visual inspections by trained staff and keeps reported faults under review.
When to test more or less often
Your own results are the best guide. HSG107 says that after the first few rounds, a low failure rate shows the interval can be lengthened and a high failure rate shows it should be shortened. Faults that cluster in one place usually point to a cause, such as the wrong equipment for the job, a harsh environment or misuse.
Some buildings need more than one regime. HSG107 gives hospitals, schools, hotels and offices as places where a kitchen or laundry needs more frequent checks than the offices next to it.
Hire stock, rented homes and new equipment
Hired-out equipment
For tool and equipment hire, HSE strongly recommends a formal inspection and test before each hire, and HSG107 adds a visual inspection when it comes back. Event production and hire firms often test far more often than once a year for this reason.
Rented homes
In Scotland, landlords must PAT test the appliances they provide before the first let and then at intervals of no more than 5 years, under the Repairing Standard guidance. The guidance adds that the retest date will usually be more frequent than every 5 years. In England, social landlords must have the equipment they provide checked at least every 5 years, under the electrical safety standards guidance. The same regulations require private landlords in England to have the wiring inspected at least every 5 years, but they do not set an interval for appliances.
New equipment
HSE says new equipment should be supplied safe and should not need a formal inspection or test, but a simple visual check is recommended to make sure it was not damaged on the way. Add it to your register with the date its first check is due. The Scottish landlord guidance takes the same line for appliances bought new less than a year before a test.
Who sets the retest date
You do. INDG236 says the person carrying out the test should not decide when the next test is due, because that decision belongs to the duty holder on a risk assessment basis. The practical answer is to set each item’s interval in your register and retest schedule, then copy that date onto the label if it has a retest box. The person testing can recommend a shorter interval, but the decision stays with you.
Turn the table into a plan
Start with an appliance register listing every item, its class and where it is used. Give each item an interval from the tables above, then put the dates in a planner. Our free retest schedule does exactly that, and the register has a column for the interval you chose.
Questions people ask
Can’t see your question here?
Does PAT testing have to be done every year?
No. HSE says the law does not require it every year. How often depends on the type of equipment and where it is used.
How often should office equipment be PAT tested?
HSE’s table suggests earthed kitchen equipment such as kettles every 1 to 2 years, and no combined test for double-insulated computers and screens, with a visual inspection every 2 to 4 years.
How often should construction site tools be tested?
Far more often than office kit. HSE’s HSG107 suggests 110V site tools are tested before first use on site and then every 3 months, and 230V tools before first use and then monthly.
How often should a landlord PAT test?
In Scotland, before the first let and then at intervals of no more than 5 years. Social landlords in England must have equipment they provide checked at least every 5 years. Your tester may recommend a shorter interval for some items.
Who decides the retest date?
You do, as the duty holder. HSE says the person carrying out the test should not decide when the next one is due, because that is a risk assessment decision.
What if I group my equipment and test it all at once?
HSE says to use the shortest testing interval in the group, or group equipment by its testing interval instead.