• Prices include VATPrices shown ex VAT
  • Free UK delivery over £100
  • Calibration certificate in every kit
  • 30-day returns, all by email
  • Purchase orders welcome
Show prices

Free PAT Testing Templates

A record sheet, appliance register, test certificate, visual inspection checklist and retest schedule. PDF and Excel, no sign-up.

PASSEDTestedRetestBy3 Nov 2026Nov 2027JS

PAT test record sheet

One page per visit. Log each item, its class, the visual check, the test results and the retest date.

Appliance register

A list of everything you own that plugs in, where it lives and when it is next due. Start here before your first test day.

PAT test certificate

A one-page summary to hand a letting agent, landlord or insurer, listing what was tested and the result.

Visual inspection checklist

The checks that find most faults before you plug anything in, from damaged cables to scorched plugs.

How to fill in a record sheet

Fill in one row per item, every time you check it. Keep the sheets with your appliance register so anyone can see what was checked and when it is next due.

  1. Asset number. The number on the item’s label, so you can find it again next year.
  2. Description and location. For example, kettle, 2nd floor kitchen.
  3. Class. I for earthed items, II for double insulated, or Lead for extension and kettle leads.
  4. Visual check. Pass or fail, and what you found if it failed.
  5. Test results. Earth continuity in ohms, insulation in megohms and leakage in milliamps, or pass and fail if your tester only shows that.
  6. Result. The overall pass or fail.
  7. Retest date. The date you have set for that item from your risk assessment. HSE says this is the duty holder’s decision, not the tester’s.
  8. Tested by. Your initials, so there is a name behind every result.

A filled-in example

Three rows as they would look after a morning’s testing with a tester that shows readings.

Asset no.Item and locationClassVisualEarth (Ω)Insulation (MΩ)Leakage (mA)ResultTested by
0012Kettle, 2nd floor kitchenIPass0.08>19.990.21PassJS
0013Laptop charger, desk 14IIPassNo test>19.99 at 250V0.02PassJS
0014Extension lead, receptionLeadFail, cracked plugNo testNo testNo testFailJS

The laptop charger is double insulated, so there is no earth test, and insulation was tested at 250V to protect its electronics. The extension lead failed its visual check, so it was not tested at all. It was labelled as a fail and taken out of use straight away.

Which template you need, and when

  • Appliance register. Start here. One line for everything that plugs in, with the interval you chose.
  • Visual inspection checklist. For the formal visual inspections between tests, which HSE says find most faults.
  • Record sheet. For each test day.
  • Retest schedule. Twelve months across the page, so you can see what is due when.
  • Test certificate. A summary to hand to a letting agent, tenant or client.

Landlords in Scotland are asked for an equipment register and a combined inspection and test record. The register and record sheet cover both.

Test it yourself

Our Starter kit has a tester with readings, labels, these templates and a calibration certificate.

See what is in a kitWhich tester? 3 questions

Questions people ask

Can’t see your question here?

Ask us by email

Answers in writingWe usually reply within one working day, Monday to Friday, so you have an answer to forward to a colleague or keep with your records.

Do I need to give my email to download them?

No. Every template downloads straight away.

Can I edit them?

Yes. The Excel versions are fully editable, and the PDFs print at A4.

Are these records a legal requirement?

No. HSE says there is no legal requirement to keep records or label equipment, but records are a useful way to show your maintenance scheme exists.